LZZBJ5-35W2/4 current transformer
LZZBJ5-35W2 type outdoor dry current transformer is suitable for rated frequency 50Hz, rated voltage 35kV power system and 27.5kV electric locomotive device, power supply gas measurement and protection, with single or polytropic ratio, multiple secondary (2. 3. four secondary) combination, high precision, large capacity, high dynamic thermal stability, moisture resistance, aging resistance, chemical corrosion resistance, high insulation performance and other advantages.
Classification:
Current transformer
Key words:
transformer
Product Description
1. Overview:
LZZBJ5-35W2 type outdoor dry current transformer is suitable for rated frequency 50Hz, rated voltage 35kV power system and 27.5kV electric locomotive device, power supply gas measurement and protection, with single or polytropic ratio, multiple secondary (2. 3. four secondary) combination, high precision, large capacity, high dynamic thermal stability, moisture resistance, aging resistance, chemical corrosion resistance, high insulation performance and other advantages.
2. conditions of use:
The ambient temperature is -25 ℃ ~ 40 ℃, and the altitude is not more than 1000 meters. It can be used in Class II filthy areas.
3. technical parameters:
1. Power factor of load COS φ = 0.8 (hysteresis)
2. Rated insulation level: 40.5/95/185kV
3. Rated secondary current: 5A or 1A
|
Rated current ratio |
|
Accurate grade and rated output (VA) |
Rated short time |
Rated dynamic stability |
Total weight |
||||
Product Model |
(A) |
Level Combinations |
Accuracy class and rated output |
Thermal current |
constant current |
(kg) |
||||
Type |
Rated Current |
Class combination |
|
|
|
|
|
(Ka) |
(Ka) |
Total |
0.2S
|
0.2
|
0.5
|
10P
|
|||||||
|
ratio |
|
Ith |
Idyn |
weight |
|||||
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
50~100/5 |
0.2S/0.5 |
20
|
20
|
25
|
30
|
150Iin |
375Iin |
|
|
|
0.2/0.5 |
|
|
|||||||
150/5 |
22.5 |
57
|
||||||||
0.2S/10P10 |
||||||||||
|
|
|
||||||||
LZZBJ5-35W2/2 |
200/5 |
0.2S/10P15 |
27.5 |
69
|
||||||
|
0.2/10P10 |
|
|
|||||||
300~400/5 |
40
|
90
|
||||||||
|
0.2/10P15 |
|||||||||
|
0.5/10P10 |
|
|
|||||||
500~800/5 |
63
|
120
|
||||||||
0.5/10P15 |
||||||||||
|
|
|
||||||||
1000~2500/5 |
80
|
160
|
||||||||
10P10/10P10 |
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
50~100/5 |
0.2S/0.5/10P10 |
20
|
20
|
25
|
20
|
150Iin |
375Iin |
|
|
|
|
|
||||||||
150/5 |
0.2S/0.5/10P15 |
22.5 |
57
|
|||||||
|
0.2/0.5/10P10 |
|
|
|||||||
200/5 |
27.5 |
69
|
||||||||
LZZBJ5-35W2/3 |
0.2/0.5/10P15 |
|||||||||
|
|
|
||||||||
300~400/5 |
0.2/10P10/10P10 |
40
|
90
|
|||||||
|
||||||||||
|
0.2/10P15/10P15 |
|
|
|||||||
500~800/5 |
63
|
120
|
||||||||
0.5/10P10/10P10 |
||||||||||
|
0.5/10P15/10P15 |
|
|
|||||||
1000~2500/5 |
80
|
160
|
||||||||
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
50~100/5 |
|
20
|
20
|
25
|
25
|
150Iin |
375Iin |
|
|
|
|
|
|
|||||||
150/5 |
0.2S0.5/10P10/10P10 |
22.5 |
57
|
|||||||
|
|
|
||||||||
200/5 |
27.5 |
69
|
||||||||
LZZBJ5-35W2/4 |
0.2S/0.5/10P15/10P15 |
|||||||||
300~400/5 |
0.2/0.5/10P10/10P10 |
40
|
90
|
|||||||
|
||||||||||
|
0.2/0.5/10P15/10P15 |
|
|
|||||||
500~800/5 |
63
|
120
|
||||||||
|
||||||||||
|
|
|
|
|||||||
1000~2500/5 |
|
80
|
160
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
Note:
1. The first item of each gear below the rated current of the multi-variable ratio current transformer is designed to be 600 ampere turns, such as 50-70-100/5
The ampere turns of each gear are 600-900-1200IN.
2.0.2S,0.2 grade: 600-900IN is 20VA, and above 900IN is 25VA. 0.5 grade: 600-800IN is 25VA,900IN above is 30VA. 10P10 grade: 600IN-900IN is 30VA, above 900IN is 40VA. 10P15 grade: 600IN-900IN is 20VA, above 900IN is 30VA.
The rated output in the table only lists the first data of each specification of the polytropic ratio. 3. The difference between the two gears before and after the current transformer is less than or equal to 2 times,
Such as 100-150-200/5,300-400-500/5, etc.
4. installation dimensions:
Outline and Dimension of LZZBJ5-35W2/4 Current Transformer
Outline and Dimension of LZZBJ5-35A/4(3) Current Transformer
Outline and Dimension of LZZBJ5-35W2/2 Current Transformer
5. Ordering Instructions:
When ordering, the product model, rated current ratio, accurate level combination and corresponding rated output, rated short-time current, etc. shall be provided. For special orders can be negotiated with the factory to resolve.
Previous Page
Next Page
Previous Page
Next Page
Recommended Products
We aim to win the market with high-quality products and win customers with honest service.
Get free product quotes